INSTALLATION (continued)
FIRE SUPPRESSION SYSTEM INSTALLATION
1. Any REMOTE MANUAL PULL STATION must be installed by an
authorized ANSUL® distributor in accordance with the
AUTHORITY
HAVING
JURISDICTION.
NOTE: If a REMOTE MANUAL PULL STATION is installed, moving
the unit for servicing will cause the Ansul® system to discharge. In
this case, the unit must only be installed with four fixed legs
(i.e. remove rear casters and replace with legs). Additional legs may
be ordered through an Authorized Wells Service Agency. See page 31.
2. The FIRE SUPPRESSION SYSTEM is comprised of a
pressurized cartridge &
container of liquid fire
suppressant, with
associated plumbing and
controls. It utilizes factory
installed FUSIBLE LINKS
for automatic actuation,
and a factory installed
MANUAL PULL STATION
for manual actuation.
Two NOZZLES are used
to disperse the liquid fire
suppression
media.
3. When the fire suppression
system activates, the fire
suppression
media
is
discharged, both the
cooking appliance and the
ventilator are de-energized,
and a buzzer will sound
continuously.
The fire suppression media
will form an emulsion
designed to both smother
and cool the fire.
Call your Authorized Ansul® Distributor immediately for
service.
NOTE:
See page 26
for the Material Safety Data Sheet for the fire
suppression
agent.
4. The MANUAL PULL STATION and any similar REMOTE MANUAL
PULL STATION will activate the fire suppression system when the
ring on the pull station is pulled horizontally.
DANGER
FIRE
HAZARD
THE FIRE SUPPRESSION
SYSTEM MUST BE
CHARGED AND CERTIFIED
BY AN AUTHORIZED
ANSUL® DISTRIBUTOR.
NEVER ATTEMPT TO
MODIFY OR BYPASS THE
FIRE SUPPRESSION
SYSTEM.
AN UNCONTROLLED FIRE
CAN CAUSE SERIOUS
INJURY, DEATH AND/OR
PROPERTY LOSS.
IMPORTANT: The FIRE
SUPPRESSION SYSTEM
must be SET-UP and
CHARGED by an authorized
Ansul® distributor before the
ventilator blower will operate.
NOTE:
If the fire suppression system
is discharged, a buzzer will
sound continuously and the
cooking appliance will
remain inoperable until the
fire suppression system is
serviced.
Recharging and resetting
must be performed by an
authorized Ansul®
distributor ONLY.
Charging of the Ansul Fire
Suppression system must be
in accordance with Ansul®
Design, Installation, Recharge
and Maintenance Manual.
(Ansul® #418087-05)
Fig. 6 Fire Suppression System