6 Commissoning, operation
WIKA operating instructions, model A-AI-2
17
A-AI-2-1:
description
to select as
output
output (out)
see chapter
no output, device is
used as display
no
off --
2-point-controller
2P
switching function
6.3.1
Min/Max alarm
AL
min/max alarm, inverse
6.3.2
A-AI-2-S:
description
to select as
output
output 1 (out 1)
output 2 (out 2)
see chapter
no output, device is
used as display
no
off off --
2-point-controller
2P
switching
function
off
6.3.1
Min-/Max-alarm,
common
AL
Min-/Max-alarm,
inverted
off 6.3.2
3-point-controller
3P
switching
function 1
switching
function 2
6.3.1
2-Punkt-Regler with
Min-/Max-alarm
2P.AL
switching
function 1
Min/Max alarm,
inverted
6.3.1
Min-/Max-Alarm,
individual
AL.F2
Max alarm,
inverted
Min alarm,
inverted
6.3.2
Press button 1 to validate the selected output function. The display shows “outP“ again.
For output function = no the configuration is now finished. Press button 1 to finish the adjustment and
to switch over to display the measuring value.
If the output function was changed here, the delay and preferred state of switching function and the
switching points / alarm-boundaries are to configured in following.
Hint:
The settings described in the following depend on the selected output function.
Depending on this setting therefore it is possible that more than one point is not
present in the following.
When pressing button 1 again, the device will display “1.dEL“ (delay = delay of switching
function 1).
Use button 2 and button 3 to set the desired value for the switching-delay.
Hint: the selected value [0.01 ... 2.00] accords the switching delay in seconds.
Press button 1 to validate the selection. The display shows “1.dEL“ again.
When pressing button 1 again, the device will display “1.Err“ (error = preferred state of
switching function 1).
Use button 2 and button 3 to set the desired initial state in case of an error.