Configuring hp sim to receive traps – HP UPS Network Module User Manual
Page 52

Systems Insight Manager integration 52
Configuring HP SIM to receive traps
Before HP SIM can receive traps, the correct MIB file (cpqpower.mib) must be compiled into HP SIM. To
download the HP Power MIB, visit the HP website
To register the MIB:
1.
Copy the MIB to the HP\Systems Insight Manager\mibs folder.
2.
From the HP\Systems Insight Manager\mibs folder, run mcompile cpqpower.mib from the
command line to compile the new MIB. A new file named cpqpower.cfg is created.
3.
Register the new MIB by entering mxmib -a cpqpower.cfg from the HP\Systems Insight
Manager\mibs command line.
4.
Enter HP\Systems Insight Manager\mibs>mxmib at the command line and verify that the new
MIB is listed.
NOTE:
For more information on uploading and registering a MIB in HP SIM, refer to the HP
Systems Insight Manager Technical Reference Guide located on the HP Management CD.
Configuring the UPS Network Module to send traps to
HP SIM
Add the HP SIM server as an SNMP trap recipient on the Trap Receivers Settings screen (on page
). The
configured server appears on the Notified Applications screen (on page