1600/6400-N4X-RD
3.0 Installation
Securely mount the Model 1600/6400-RD enclosure.
Model 6400-N4X-RD
Gas Detection Control System
Remote Display
9.0"
11.85"
Mounting feet
13.2"
13.73"
6.47"
6.78"
R
R
Figure 1 Dimensional
Connect 110/220VAC input wiring to the terminals labeled “VAC (L1)”, “Neutral (L2)”, and “Ground” (See
Figure 2). For 220Volt Units connect L1 to the terminal labeled “VAC (L1)”, L2 to the terminal labeled
“Neutral (L2)” and Ground to the terminal labeled “Ground”. The Power Supply is capable of handling AC
inputs from 100-240VAC 50-60Hz with no degradation.
Connect the RS-485 wiring from The 6400 Control Unit to the terminals located on the Back Panel. These
terminals are labeled “A” (+), “B” (–), and “Shld” (shield) for primary RS-485 communication (Figure 2).
RS-485 wiring should consist of a two conductor, shielded twisted pair (Belden P/N 9841).
Optionally, the Remote Alarm Reset Switch can be connected to the Model 1600/6400 Controller’s Remote
Reset Terminal Blocks (Labeled “Remote Reset”). The Switch provides easy access to the controllers Alarm
Reset, without having to access the controller.