beautypg.com

External interfaces – Proface APL3000B - Node Box PC User Manual

Page 8

background image

8

External Interfaces

• This PS-B unit’s serial port is not isolated. When the host (PLC) unit is also not

isolated, and to reduce the risk of damaging the RS-232C/RS-422/RS-485 circuit, be
sure to connect the #5 SG (Signal Ground) terminal.

„ Serial Interface (COM1, COM2)

‹COM1

‹COM2

COM2 can be changed to either RS-232C,
RS-422 or RS-485. (The factory setting is
RS-232C.)

To change this setting, set Serial

Mode Select switch on the circuit board to the
desired position.
Please refer to "Switches" for details.

Interfit Bracket

#4-40 (UNC)

Pin

#

RS-232C

Signal Name

Meaning

1

CD

Carrier Detect

2

RD (RXD)

Receive Data

3

SD (TXD)

Send Data

4

ER (DTR)

Data Terminal Ready

5

GND

Signal Ground

6

DR (DSR)

Data Set Ready

7

RS (RTS)

Request to Send

8

CS (CTS)

Clear to Send

9

CI (RI)

Called status display

FG FG

Frame Ground
(Common with SG)

Pin

#

RS-232C

Signal Name

Meaning

1

CD

Carrier Detect

2

RD (RXD)

Receive Data

3

SD (TXD)

Send Data

4

ER (DTR)

Data Terminal Ready

5

GND

Signal Ground

6

DR (DSR)

Data Set Ready

7

RS (RTS)

Request to Send

8

CS (CTS)

Clear to Send

9

CI (RI)/
+5V

*1

Called status display/
+5V Output
(Switching available)

FG FG

Frame Ground
(Common with SG)

*1 To change the RI/+5V setting of #9 pin set

System Set switch to the desired position.

Pin

#

RS-422

Signal Name

Meaning

1

RDA

Receive Data A (+)

2

RDB

Receive Data B (-)

3

SDA

Send Data A (+)

4

NC

No Connection

5

GND

Signal Ground

6

NC

No Connection

7

SDB

Send Data B (-)

8

NC

No Connection

9

NC

No Connection

FG FG

Frame Ground
(Common with SG)

Pin

#

RS-485

Signal Name

Meaning

1

DATA +

Send/Receive
Data(+)

2

DATA -

Send/Receive Data(-)

3

NC

No Connection

Pin

#

RS-232C

Signal Name

Meaning