Detroit Radiant Products Company HLV Series User Manual
Page 9
9
HLV
Series
Model Number
Mounting
Angle*
Sides
Front
Behind
Top**
Below
HLV-40, HLV-50 [N, P]
0°
9
9
4
47
45°
39
8
10
47
with 1 side shield
0°
29
8
4
47
with 2 side shields
0°
9
9
4
47
20 ft. from burner
0°
7
7
4
30
HLV-60, HLV-75 [N, P]
0°
9
9
4
48
45°
39
8
10
48
with 1 side shield
0°
29
8
4
48
with 2 side shields
0°
9
9
4
48
20 ft. from burner
0°
7
7
4
30
HLV-80 [N, P]
0°
11
11
4
48
45°
39
8
10
48
with 1 side shield
0°
29
8
4
48
with 2 side shields
0°
16
16
4
48
20 ft. from burner
0°
7
7
4
30
HLV-90 [N, P]
0°
12
12
4
54
45°
39
8
10
54
with 1 side shield
0°
29
8
4
54
with 2 side shields
0°
16
16
4
54
20 ft. from burner
0°
7
7
4
30
HLV-100 [N, P]
0°
14
14
4
66
45°
39
8
10
66
with 1 side shield
0°
29
8
4
66
with 2 side shields
0°
16
16
4
66
20 ft. from burner
0°
7
7
4
30
HLV-110, HLV-120, HLV-125 [N, P]
0°
18
18
4
72
45°
58
8
10
72
with 1 side shield
0°
42
8
4
72
with 2 side shields
0°
20
20
4
72
20 ft. from burner
0°
7
7
4
30
HLV-140, HLV-150 [N, P]
0°
24
24
6
81
45°
58
8
10
81
with 1 side shield
0°
42
8
6
81
with 2 side shields
0°
30
30
6
81
20 ft. from burner
0°
11
11
6
44
HLV-170, HLV-175 [N, P]
0°
34
34
6
92
45°
63
8
10
92
with 1 side shield
0°
50
8
6
92
with 2 side shields
0°
30
30
6
92
20 ft. from burner
0°
11
11
6
44
HLV-180, HLV-200 [N, P]
0°
41
41
6
94
45°
63
8
10
94
with 1 side shield
0°
54
8
6
94
with 2 side shields
0°
30
30
6
94
20 ft. from burner
0°
11
11
6
44
1.0
Introduction
•
Clearance to Combustibles
Chart 1.2 •
Clearance to Combustibles in Inches (see Figure 1.2 for Mounting Angles)
*
Heaters mounted on an angle between 0° to 45° must maintain clearances posted for 0° or 45°; whichever is greater.
**
The top clearance of an exposed tube connection to combustibles is 18 inches.