beautypg.com

Notice – Detroit Radiant Products Company HLV Series User Manual

Page 47

background image

NOTICE

Bypassing any switch is intended for testing purposes only. Do not leave switch
bypassed during normal operation or the heater’s built-in safety mechanisms will be
compromised.

47

HLV

Series

After the system has run for 20 minutes in high fire mode, measure box pressures

using a manometer with an adequate range.

Do the setpoints correspond with Chart 4.2 on page 44?

5.0

Maintenance • Troubleshooting Guide

Is the panel supplying

120V/220v to the exhauster?

Is there 24V on the secondary side of the

transformer located in the panel assembly?

No

Yes

The exhauster is faulty and

must be replaced.

Replace

transformer.

No

Yes

A faulty relay may exist in the

panel assembly. Consult factory.

Is the ignitor

physically damaged?

Replace ignitor.

Yes

Check voltage during ignition sequence (usually 5

seconds after power to burner control box). Is it 24V?

No

Is the resistance through

the ignitor 1 to 6

?

Replace faulty

wiring.

Replace

ignitor.

Yes

No

Yes

Is the inlet or the outlet of

the unit obstructed?

No

Remove

obstruction.

Yes

Check for loose wiring or

restrictions in hose connections to

the pressure switch. Are they OK?

No

Repair wiring or hose

connections.

Yes

Temporarily place a jumper across the

terminal of the safety pressure switch.

Set control box cover in place.

Does the ignitor glow red?

Yes

No

Adjust dampers until

proper box pressures

are achieved.

Yes

Is there 24V on the

secondary side of the

transformer in the burner

control box?

Replace faulty transformer. Note: The original

transformer is equipped with an automatic

resetting fuse. Confirm fuse has not been tripped.

No

No

Yes

Is there 24V between

L1 and ground at the

circuit board?

No

Replace faulty

wiring.

No

Replace circuit board.

Yes

*

*