HLV

Series

Does the ignitor warm

up and glow red?

Does the exhauster

fan turn on?

5.0

Maintenance • Troubleshooting Guide

Turn up thermostat

Is the power at the

exhauster 120V/220V?

No

Yes

Continued on page 48

No

Is the thermostat supplying 24V

to the exhauster control panel?

Find the source of the

electrical problem

No

Is power at the burner

control box 120V/220V?

No

Yes

Is the thermostat supplying

24V to the terminal plug on the

burner control box?

Yes

No

Find the source of the

electrical problem.

Yes

No

Find the source of the electrical

problem between the thermostat

transformer, thermostat and panel.

Yes

Replace the pressure switch

after verifying:

• Baffle(s) are in the radiant tube
furthest from the burner.
• Heater, fan blowers ,squirrel cage,
intake and exhaust are clean and
free from dirt and obstructions.
• The 4” air intake pipe does not
exceed 20 ft. and/or 2 elbows.
• There is not a negative pressure
experienced at the area of air
intake (e.g.; high winds, attic

space, tightly sealed building).

After the ignitor is fully

energized, does the gas

valve open?

Yes

Test for 24V at valve opening period (usually 5 seconds after

power to the burner control box). Is there 24V at the valve?

No

Replace circuit board

and/or wiring harness.

Yes

Check to confirm gas pressure is

within minimum and maximum inputs

as indicated on the heater’s rating

plate. Is gas pressure OK?

No

Correct problem.

Replace gas valve.

Yes

No

Find the source of the electrical

problem between the thermostat

transformer, thermostat and panel.

HLV Series Troubleshooting Guide

Yes