Detroit Radiant Products Company HLV Series User Manual
Page 38
38
HLV
Series
3.0
Installation
•
Electrical Requirements
•
Pump & Panel Wiring
120V (230V Opt.)
TRANSFORMER
24V
BL
4
3
2
1
2
4
6
8
1
24V COIL
0
NC
NO
COM
24V COIL
COM
24V COIL
NO
NC
(IF USED)
24V INPUT
FOR ZONE #1
O
GY
GY
O
R
N
G
L1
R
W
230VAC INPUT
OPTIONAL
(FACTORY ORDERED)
W
G
BL
BL
Y
Y
BL
BL
R
R
W
BK
BL
W
24V INPUT
FOR ZONE #2
120VAC
NOTE: In North America, the pump and panel are pre-wired at the factory for 120V. If an alternate voltage
is to be used consult the factory.
Wiring from the power supply to the panel and pump must be 12 AWG or larger to maintain proper voltage
under full load conditions.
The circuitry for the panel and pump is suitable for a 20 AMP circuit maximum.
Figure 3.25 •
Pump and Panel Assembly Internal Wiring