3.0

Installation

Tube Assembly and Mounting

Common Accessories

10.5”

12.5”

Elbows and Intersections

Elbows and intersections are common components in a tube heater vacuum system. Refer to Chart 3.2
for minimum distance requirements from the burner control box for these accessories.

Note: Proper tee usage is critical. Refer to the HLV Series Accessory Book for additional system
accessories and options.

90° Elbow
(P/N: E6)

Figure 3.9

Common Tube Connections

Individual Burner Input (BTU/h)

Minimum Distance

40,000 to 60,000

10 ft.*

75,000 to 80,000

10 ft.*

90,000 to 100,000

10 ft.*

110,000 to 125,000

10 ft.*

140,000 to 150,000

15 ft.*

170,000 to 180,000

15 ft.*

200,000

20 ft.

In-line Tee
(P/N: V-TI)

Cross
(P/N: V-CR)

Chart 3.2

Minimum Distance From Burner to First Elbow or Intersection (covered with reflector*)

Figure 3.10

Common Accessory Dimensions

90° Elbow

P/N: E6

12.5”

Tee

P/N: V-T or V-TI

Cross

P/N: V-CR

Damper

P/N: V-D

11.5”

1’-9”

1’-4”

4”

4”

10.5”

Tee
(P/N: V-T)

Flow

* Exposed tube connections (elbow, tees,
u-bends and intersections not covered
with a reflector) cannot be placed less
than 20 feet downstream of burner. The
top clearance of an exposed tube
connection to combustibles is 18 in.