Design • Vacuum Pump Application

Vacuum Pump Application

• The vacuum pump vent length must be from 2 ft. to 25 ft.
• The maximum number of elbows in the vent system is two.
• Both isolation boots provided with the system must be installed prior to the vacuum pump (Figure 3.2).

Vacuum pump selection is based on the overall BTU/H input of each system. Refer to Chart 2.3 for
vacuum pump determination.

Example:

A system designed with one HLV-150 burner and two HLV-100 burners has an overall system input
of 350,000 BTU/h. This system requires the PB-9 vacuum pump as indicated in Chart 2.3.

Model

No.

Total System Input

Range (BTU/h)

Allowable Burners

per Pump

Weight

Dimensions

(See Figure 2.11)

A

B

C

NC-7

40,000 to 150,000

1 min. / 2 max.

20 lbs.

10.0”

16.0”

18.5”

PB-8

50,000 to 275,000

1 min. / 4 max.

60 lbs.

11.0”

19.75”

16.5”

PB-9

280,000 to 545,000

2 min. / 6 max.*

67 lbs.

14.5”

19.75”

16.5”

PB-10A

550,000 to 750,000

3 min. / 6 max.*

73 lbs.

17.5”

21.0”

20.0”

Chart 2.3 •

Vacuum Pump Models

Figure 2.11 •

Vacuum Pump Dimensions

(see chart 2.3)

B

C

B

NC-7 Pump

Side View

NC-7 Pump

Front View

PB Series Pumps

Isometric View

* Consult factory if exceeding maximum burners is required.

NOTE: The average sound level of PB Series vacuum pumps is between 60 and 63 DBA. If the

application requires a lower decibel level, relocation of the vacuum pump or a sound-deadening enclosure
may be necessary. Contact factory.