System design definitions – Detroit Radiant Products Company HLV Series User Manual

Page 14

background image

14

HLV

Series

2.0

Design

System Design Definitions

System Design Definitions

Calculated Maximum Run:

The longest allowable ‘Calculated Run’ from any burner to the vacuum pump, including condensing pipe.

Calculated Minimum Run:

The shortest allowable ‘Calculated Run’ from any burner (including V-TTS Tandem Tee runs) to the vacuum pump,
including condensing pipe.

Calculated Run ***read carefully***

:

Calculated run is determined by adding the total ‘Single Flow’ plus

one-half of the ‘Common Flow’ of tubing/pipe

from any burner to the vacuum pump.

Calculated Starting Point of Condensing Run:

The point in the ‘Calculated Run’ where condensing pipe must begin. See Figure 2.3.

Common Flow:

The tube/pipe in a run between the first intersection (tee or cross) and the vacuum pump. ‘Common Flow’ begins
at the point where two or more burners share common tube/pipe. See Figure 2.2.

Minimum Distance to Elbow or Intersection:

The minimum allowable distance from a burner to the first elbow or intersection.

Run:

The total

actual length of tube/pipe from an individual burner to the vacuum pump.

Single Flow:

The tube/pipe in a run from the burner to the first intersection (tee or cross). See Figure 2.3.

Figure 2.2 •

Single and Common Flow

Figure 2.3 •

Starting Point of Condensing Pipe

Com

mon

F

lo

w

Single Flow

Single Flow

20 ft.

HLV-75

HLV-75

Vacuum Pump

30 ft.

30 ft.

HLV-75

HLV-75

Vacuum Pump

20 ft.

40 ft.

40 ft.

40 ft.

Starting Point of Condensing