beautypg.com

Detroit Radiant Products Company HLV Series User Manual

Page 13

background image

13

HLV

Series

2.0

Design

Design for Condensing Systems

4

Measure the ‘Calculated Minimum Run’ for each burner. It is generally recommended to shorten

runs which exceed the ‘Calculated Maximum Run’. Refer to Figures 2.2 & 2.3 on p.14 for

examples of determining ‘Calculated Maximum Run’.

5

TEMPERATURE ZONES: In systems where dual zones will be used to control burners on separate

thermostats, the following guideline must be met:

a) Condensing pipe must begin at the point where two runs (operating on separate zones)

share common tubing; continuing to the pump. See Figure 2.1.

6

Confirm the following applies (condensing systems only):

a) A maximum of three elbows per run is allowed per system.

b) A maximum of six intersections (tees or crosses) are allowed per system.

c) All elbows and intersections less than 20 feet from a burner requires a reflector.

Figure 2.1 •

Condensing Pipe for Dual Zone Systems and Simulated In-Line Burners

T

T

Condensing Pipe

Points where zone 1 & 2 share

common tubing. Condensing

pipe must begin here.

Zone 1

Zone 2

Condensing Pipe

Tie-In Burner