QTS

Series

38

5.0

Maintenance

Troubleshooting Guide

Continued from page 36.

Troubleshooting ends.

Do the burners stay on for approx.

15 seconds and then shut off?

Do the burners come on and turn
off immediately (1 to 2 seconds)?

Test for 24V at valve opening period (usually 7 to 10 seconds

after power to heater). Is there 24V to valve for 15 seconds?

Yes

The following can cause the heater to shut down:

• Improper grounding.
• High winds.
• Dirty environment.
• Fluctuating gas pressure.

Do the burners

stay on?

No

Does the heater stay on

until the call for heat ends?

Yes

Yes

No

No

Yes

No

Diagnostic Indicator

LED

MODE

1 Flash

Start up.

2 Flashes

Flame. No call for heat.

3 Flashes

Ignition lockout.

4 Flashes

Valve relay lockout.

Replace circuit board.

Yes

No

Yes

Yes

No

Contact factory.