If an error code is displayed, or odd behavior of the unit occurs, the fi rst corrective action should be to “Cycle the Power”:
Unplug the 120Vac power cord and after 5 seconds plug it in again. If this doesn’t clear the fault, proceed with the
“Remedy” in the following table (Table 5).

If wire harness checking is required, examine the integrity of wires themselves, the connector housings, the integrity of
the terminals as well as condition of the crimps.

Fault

Code

Displayed

Description

Cause

Lockout

type

Remedy

E01, E02

Invalid Rated
KBtu/Model Type.

Control detects that the
confi guration selected is not
defi ned or the confi guration
has never been set.

Continuous

Change the main controller board
(board).

E03, E04,

E05, E06

Main Valve Relay
Out Of Sequence.

Control detects that a relay
used to enable the Main
Valve has failed in either the
open or closed position.

Soft

Change the board.

E07

Flame Detected.

Flame detected when no
fl ame was expected.

Soft

Check the fl ame rod.
Check the fl ame wire harness.
Change the board.

1.
2.
3.

E08

ECO switch is
open.

Control detects that the
ECO switch is open,
preventing power to the
Main Valve.

Continuous

Measure the water temperature.
ECO switch open temperature
is 85±5ºC (185±14ºF) and close
temperature is 65±5ºC (149±14ºF).
Check the ECO switch.
Check the ECO wire harness.
Change the board.

1.

2.
3.
4.

E09

High temperature
Vent Switch Open.

Control detects that the High
Temperature Vent Switch is
open, preventing power to
the Main Valve.

Continuous

Measure the water temperature.
High Vent Switch open temperature
is 74±2.8ºC (165±5ºF) and close
temperature is 57±2.8ºC (135±5ºF).
Check the switch.
Check the High Vent Switch wire
harness.
Change the board.

1.

2.
3.

4.

E10

120Vac too high.

120Vac > Overvoltage Limit.

Auto Reset

Nominal voltage is 120Vac.
Overvoltage limit is 132Vac,
Undervoltage limit is 102Vac.

Check the power cord.
Check the wall outlet.
Measure the voltage at the board
connector J7 between pin1 and pin
3. If the voltage is between limits,
change the board.

1.
2.
3.

E11

120Vac too low.

120Vac < Undervoltage
Limit.

E12

Blower Current
abnormal.

Blower Current meets
requirements for a
completely blocked fl ue.

Soft

Check the venting system. If the
venting system is clear, recalibrate
the unit.
Check the blower wire harness.
Change the blower.
Change the board.

1.

2.
3.
4.

E13

Blower Current meets
requirements for a partially
blocked fl ue.

E14

Blower Current meets
requirements for a non-
heating blocked fl ue
evaluation.

TABLE 5