TRIO DT 250 - TRIO DT 350
17/10/12 - 300028005-001-03
5.4 LED message code
Continuously green
At least one relay is closed.
Regulation operating normally (System Operating). Solar system
Operating. The temperature of the hot water tank (parameter TS)
increases.
Continuously red
All relays are open.
The installation is stopped. The solar collectors are not hot enough
(parameter TC) to enable operation.
Flashing green/red
- Initialisation phase
- Sensor fault.
See chapter Sensor fault.
- The installation is in manual mode.
For automatic operation, set parameter MM to 4.
- Maximum tank temperature exceeded.
The hot water tank has reached the set temperature and the
installation is in overheating safety mode or in cooling mode.
- Maximum temperature of the solar collectors exceeded.
The installation is in safety mode. It remains in this mode until the
temperature of the solar collectors has fallen back below the
maximum temperature.
5.5 Measured values and adjustment parameters
The regulator has a safety system that cuts off the tank at
temperatures of over 80°C.
Channel
Abbreviation
Range
Increment
Factory setting
Collector temperature
TC
[-50.0 ... 250.0] °C
-
-
Calorifier temperature
TS
[-50.0 ... 250.0] °C
-
-
Amount of heat
kWh
[0 ... 9999] kWh
-
-
Pump regime
PC
[0 ... 100] %
-
-
Self-calibration time
tc
[0 ... 5] minutes
-
-
Return temperature
TR
-50...250°C
-
-
Additional temperature
TM
-50...250°C
-
-
Type of installation
ANL
Installation 1
Installation 2
-
Installation 1
Temperature difference enabling the passage of the heating
return via the solar tank
DO
[0.5 ... 19.5] K
0.1
6
Temperature difference enabling heating return directly to the
boiler
DF
[0.4 ... 19.5] K
0.1
4
Reference temperature difference
DT
[10 ... 20] K
0.1
20
Zone changeover temperature (tank)
SZ
[20 ... 80] °C
0.1
55
Set temperature of the solar calorifier
SX
[20 ... 80] °C
0.1
60
Maximum collector temperature
CX
[100 ... 125] °C
0.1
100 °C
Self-calibration phase
tu
[1 ... 5] minutes
1
3
Pump minimum speed
PN
[50 ... 100] %
5
50
Tubular solar collector function
FT
[0 ... 1]
1
0
Maximum flow rate
Fx
[0 … 20] l/min
0.1
Installation 1: 6.7
Installation 2: 4.2
Manual mode
MM
[0 ... 4]
1
4
Software version
VN
-
-
1
Hardware version
PG
-
-
64.30
Measured values
Adjustment parameter