beautypg.com

Atec TTC-2000 User Manual

Triac controllers type ttc 2000, J.09, Ttc 2000

background image

J.09

Heating and
cooling batteries

TTC 2000

Controller
Electrical

Accessories

TG-A130
Clamp-on temperature sensors
TG-K330
Duct temperature sensors
TG-K360
Duct temperature sensors
TG-R430
Room temperature sensors
(adjustable)
TG-R530 REGIN
Room temperature sensors

www.airtradecentre.com

Triac controllers type TTC 2000

Triac controller for wall mounting  with setpoint adjustment for controlling 3-phase
electric heating batteries, it is possible to connect an external sensor to the controller,
it is also possible to let the controller run against an external 0 - 10 V DC signal

Application

 

Electric heating batteries

Specifications

 

Possible to connect 230 V or 400 V 3-phase electric heaters

 

Maximal load : 9,5 kW (230V) or 16,5 kW (400V)

 

Room temperature control : for slow temperature changes, works as P-controller
(P = 2K)

 

Supply air temperature control : for rapid temperature changes, works as PI-
controller (P = 20K, reset time = 6 min)

 

Settable cycle time : 6 to 120 s

 

Min/max limit possible : 0 to 60°C

Mounting

 

Wall

Accessoires

 

Duct temperature sensors,

Type TG-K330

 

Room temperature sensors,

Type TG-R530

 

Min/max temperature sensors,

Type TG-K360

 

Room temperature sensors for external setpoint,

Type TG-R430

Technical data

 

Supply voltage : 230V AC or 400V AC, 3-phase. Automatic adaptation

 

Current : minimum 3 A - maximum 25 A

 

IP 30

 

Proportional band : 2K fixed (room control) / 20K fixed (supply air temperature
control)

 

Reset time : 6 minutes, fixed (supply air temperature control)

 

Pulse period : 6 to 60 s

J.09 TTC 2000 1/2 - 2012/8/19 - AA-EN