Atec TTC-2000 User Manual
Triac controllers type ttc 2000, J.09, Ttc 2000
J.09
Heating and
cooling batteries
TTC 2000
Controller
Electrical
Accessories
TG-A130
Clamp-on temperature sensors
TG-K330
Duct temperature sensors
TG-K360
Duct temperature sensors
TG-R430
Room temperature sensors
(adjustable)
TG-R530 REGIN
Room temperature sensors
www.airtradecentre.com
Triac controllers type TTC 2000
Triac controller for wall mounting with setpoint adjustment for controlling 3-phase
electric heating batteries, it is possible to connect an external sensor to the controller,
it is also possible to let the controller run against an external 0 - 10 V DC signal
Application
Electric heating batteries
Specifications
Possible to connect 230 V or 400 V 3-phase electric heaters
Maximal load : 9,5 kW (230V) or 16,5 kW (400V)
Room temperature control : for slow temperature changes, works as P-controller
(P = 2K)
Supply air temperature control : for rapid temperature changes, works as PI-
controller (P = 20K, reset time = 6 min)
Settable cycle time : 6 to 120 s
Min/max limit possible : 0 to 60°C
Mounting
Wall
Accessoires
Duct temperature sensors,
Type TG-K330
Room temperature sensors,
Type TG-R530
Min/max temperature sensors,
Type TG-K360
Room temperature sensors for external setpoint,
Type TG-R430
Technical data
Supply voltage : 230V AC or 400V AC, 3-phase. Automatic adaptation
Current : minimum 3 A - maximum 25 A
IP 30
Proportional band : 2K fixed (room control) / 20K fixed (supply air temperature
control)
Reset time : 6 minutes, fixed (supply air temperature control)
Pulse period : 6 to 60 s
J.09 TTC 2000 1/2 - 2012/8/19 - AA-EN