EMISSIONS DATA

EPA TIER-2 2006 - ---- *************************************************** B5
Gaseous emissions data measurements are consistent with those described in
EPA 40 CFR PART 89 SUBPART D and ISO 8178 for measuring HC, CO, PM, and NOx

Gaseous emissions values are WEIGHTED CYCLE AVERAGES and are in compliance
with the following non-road regulations:

LOCALITY AGENCY/LEVEL MAX LIMITS - g/kW-hr
----------------- ------------ -----------------------------------
U.S. (incl Calif) EPA/TIER-2 CO:3.5 NOx + HC:6.4 PM:0.2

REFERENCE EXHAUST STACK DIAMETER

--

WET EXHAUST MASS

13,789.9 LB/HR

WET EXHAUST FLOW (964.40 F STACK TEMP )

8,390.77 CFM

WET EXHAUST FLOW RATE ( 32 DEG F AND 29.98 IN HG )

2,840.00 STD CFM

DRY EXHAUST FLOW RATE ( 32 DEG F AND 29.98 IN HG )

2,601.63 STD CFM

FUEL FLOW RATE

74 GAL/HR