STARTING CAPABILITIES (sKVA)

FUEL

Natural Gas

Propane Vapor

Single-Phase 120/240VAC @1.0pf

100

Amps: 417

100

Amps: 417

Three-Phase 120/208VAC @0.8pf

100

Amps: 347

100

Amps: 347

Three-Phase 120/240VAC @0.8pf

100

Amps: 301

100

Amps: 301

Three-Phase 277/480VAC @0.8pf

100

Amps: 150

100

Amps: 150

Three-Phase 346/600VAC @0.8pf

100

Amps: 120

100

Amps: 120

sKVA vs. Voltage Dip

480VAC

208/240VAC

Alternator

kW

10%

15%

20%

25%

30%

35%

10%

15%

20%

25%

30%

35%

Standard

100

79

118

157

197

236

275

59

89

118

148

177

206

Upsize 1

130

116

174

232

290

348

406

87

131

174

218

261

305

COOLING

COMBUSTION AIR REQUIREMENTS

ENGINE

EXHAUST

STANDBY

Flow at Rated Power

cfm

282

STANDBY

Rated Engine Speed

rpm

1800

Horsepower at Rated kW**

hp

149

Piston Speed

ft/min

1275

BMEP

psi

103

** Refer to “Emissions Data Sheet” for maximum bHP for EPA and SCAQMD permitting purposes.

STANDBY

Exhaust Flow (Rated Output)

cfm (m

3

/min)

866 (24.5)

Maximum Recommended Back Pressure

inHg

1.5

Exhaust Temp (Rated Output)

ºF (ºC)

1200 (649)

Exhaust Outlet Size (Open Set)

in

2 1/2 x 2

POWER RATINGS (kW)

Fuel Consumption Rates*

Natural Gas

Propane Vapor

Percent Load

ft

3

/hr

m

3

/hr

Percent Load

ft

3

/hr

gal/hr

m

3

/hr

25%

380

10.8

25%

174

4.8

4.9

50%

608

17.2

50%

273

7.5

7.7

75%

837

23.7

75%

370

10.2

10.5

100%

1066

30.2

100%

464

12.8

13.1

* Refer to "Emissions Data Sheet" for maximum fuel flow for EPA and SCAQMD permitting purposes.

STANDBY

Air Flow (inlet air combustion and radiator)

ft

3

/min (m

3

/min)

5797 (164.2)

System Coolant Capacity

Gal (Liters)

6 (22.7)

Heat Rejection to Coolant

BTU/hr

159,996

Max. Operating Air Temp on Radiator

ºF (ºC)

122 (50)

Max. Ambient Temperature

ºF (ºC)

104 (40)

Maximum Radiator Backpressure

in H

2

O

0.50

3 of 5

G100LG

operating data (60Hz)

G100LG 100kW

Deration – Operational characteristics consider maximum ambient conditions. Derate factors may apply under atypical site conditions. All performance ratings in accordance with ISO3046,
BS5514, ISO8528 and DIN6271 standards.