4 Mounting
VEGASOURCE 31 •
38131-EN-130415
Recommended orientation
40°/20°
5°
1
2
Fig. 17: Correct mounting of the fire-proof version
1 Mounting with level measurement
2 Mounting with level detection
The source holder is also available as a fire-proof version (821 °C for
30 min./1510 °F for 30 min.). This version has an expansion tank.
Mount the source holder in such a way that the expansion tank is on
top, i.e. in the highest position.
In case of fire, the molten lead can expand to the expansion tank and
just closes the channel of the exit beam.
Note:
After a fire, the shielding in the upper area of the protective vessel is
slighly reduced. Contact our consultants concerning the exchange of
the source holder.
Orientation with lack of space
40°/20°
5°
1
2
Fig. 18: Installation of the fire-proof version when space above the source
container is limited
1 Mounting with level measurement
2 Mounting with level detection
Due to lack of space above the source holder, the source holder can
be also mounted in such away that the expansion tank is below or
laterally.
In case of fire, the molten lead can expand to the expansion tank and
hence fills the exist channel and the expansion tank.
Warning:
After a fire, the shielding in the upper area of the source container is
considerably reduced. The system may no longer be operated. The
source container must be exchanged immediately.
Fire-proof version