Installation guide, Wiring example – Veris Industries H535NS Install User Manual
Page 3

Z202807-0D
PAGE 3
©2012 Veris Industries USA 800.354.8556 or +1.503.598.4564 / [email protected]
07121
Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.
TM
INSTALLATION GUIDE
H535NS
Wiring example
C
N.C.
N.O.
1.
Relay Contacts:
Wire the H535NS in series with the motor using these terminals.
Choose from N.O. or N.C.
2.
Relay:
Enables actuation of the circuit by a control system
3.
Relay Coil Terminal Blocks:
Wire the output signal from the control panel to
actuate the relay. 24 VAC/DC; 36 mA nominal
4.
Relay Status LED:
For positive indication of energized coil.
CAUTION!
Do not rely on status indicators to determine whether or not the relay contacts are
connected to a power source. Doing so may result in injury or death from electrical
shock.
If the connections to the unit are made through more than one metallic conduit, bond
the conduits to prevent the hazard of electric shock. A bonding plate is available (Veris
part AH10).
c.) surface mounting:
Line Voltage
Wires
Connect line voltage wires
to line current terminals
Wire the 12 AWG lines from the controller through the side of the device, onto
the line current terminals. Tighten line current terminal blocks to 12 in-lb
(1.35 N-m) torque.
d.) nipple mount to another enclosure:
Insert the conduit nuts (provided) into the slots in the side hole of the device
for additional weight support.
Connect line voltage wires
to line current terminals
ENCLOSURE
Nipple to existing enclosure
(conduit nipple fitting not
provided)
Line voltage wires
Wire the 12 AWG lines from the controller through the side of the device,
from the enclosure to the line current terminals. Tighten line current terminal
blocks to 12 in-lb (1.35 N-m) torque.
5. Use the knockout seal to cover any unused holes in the housing. Attach the cover,
securing with the screws provided.
NOTE: If a conduit is used, connect the conduit to the mounting hub before connecting it to the
device. Be sure to support the H535NS housing when nipple-mounted to another enclosure, or the
unit may shift on opening, potentially causing undue stress on the wiring and the terminals.