Adding or replacing internal batteries, Danger, Caution – Tripp Lite SURBC2030 User Manual

Page 2: Warning, Internal battery pack wiring diagram

background image

UPS System

Battery Back

Connector

White wire

Blue wire

UPS System

Battery Back

Connector

Fuse Block Bracket

Red wire (+)

Black wire (–)

2

Adding or Replacing Internal Batteries

DANGER!

POTENTIALLY LETHAL HIGH VOLTAGE! FOR QUALIFIED ELECTRICIANS ONLY!

Follow all safety precautions in the Safety section before adding or replacing internal batteries.

DANGER!

DO NOT REMOVE BATTERY SLEEVE!

Do not remove the plastic sleeve covering the battery strings. The sleeve is designed to prevent accidental contact with the
terminals on the individual batteries. Contact with the terminals will create a potential for serious injury or death from lethal
high voltage. Do not allow tools or other metal objects to come in contact with the terminals.

CAUTION!

BATTERY PACKS ARE HEAVY!

Use assistants as needed.

WARNING!

CHECK BATTERY PACK VOLTAGE BEFORE COMPLETING INSTALLATION

Do not install battery packs with DC voltages outside the acceptable range. (They may compromise battery backup
capabilities).

NOTE!

Each battery pack consists of two strings of batteries: one string with a BLACK cable and one string with a RED cable.

The batteries are designed for hot-swap replacement, which
allows connected equipment to continually receive AC mains
power (but not battery backup support in the event of a
blackout) during the battery installation procedure. See
“Operation of Manual Bypass Switch” in the Operation section
of the UPS System’s owner’s manual. Although the batteries
can be hot-swapped, qualified service personnel may want to
completely turn the UPS off during battery installation. See
“Turning the UPS Off” in the Operation section of the UPS
System’s owner’s manual.

Internal battery packs must be replaced by equivalent batteries
available from Tripp Lite. Adding battery packs will increase
recharge time. Individual models may vary slightly from
diagrams.

INTERNAL BATTERY PACK WIRING
DIAGRAM

Qualified service personnel should familiarize themselves with
the battery pack wiring diagram prior to adding or replacing
batteries. The battery module can accept up to four battery
packs (each pack consisting of two strings). The diagram
shows all four battery packs connected for illustrative
purposes only. The actual number of batteries shipped with the
UPS System varies depending on model number.