beautypg.com

Caution, 3. outdoor unit – Toshiba RAS-10SKV-A User Manual

Page 56

background image

– 55 –

FILE NO. SVM-07008

10

-3-2. Refrigerant piping connection


1. Cut the pipe with a pipe cutter.

Fig. 10-3-2

2. Insert a flare nut into the pipe, and flare the pipe.

Projection margin in flaring : A (Unit : mm)

Fig. 10-3-3

ial (wing nut type)


Align the centers of the connecting pipes and tighten

the flare nut as far as possible with your fingers. Then

tighten the nut with a spanner and torque wrench as

shown in the figure.

Fig. 10-3-4

10-3. Outdoor Unit

10-3-1. Installation place

A place which provides the spaces around the
outdoor unit as shown in the left diagram.

A place which can bear the weight of the outdoor
unit and does not allow an increase in noise level
and vibration.

A place where the operation noise and discharged
air do not disturb users neighbors.

A place which is not exposed to a strong wind.

A place free of a leakage of combustible gases.

A place which does not block a passage.

When the outdoor unit is to be installed in an
elevated position, be sure to secure its feet.

An allowable length of the connecting pipe is up
15 m.

An allowable height level is up to 10 m.

A place where the drain water does not raise any
problem.

CAUTION

1. Install the outdoor unit without anything blocking

the air discharging.

2. When the outdoor unit is installed in a place

exposed always exposed to strong wind like a
coast or on a high storey of a building, secure
the normal fan operation using a duct or a wind
shield.

3. In particularly windy areas, install the unit such

as to avoid admission of wind.

4. Installation in the following places may result in

trouble.
Do not install the unit in such places.

A place full of machine oil.

A saline-place such as the coast.

A place full of sulfide gas.

A place where high-frequency waves are likely
to be generated as from audio equipment,
welders, and medical equipment.

Fig. 10-3-1

Strong

wind

CAUTION

Do not apply excess torque.

Otherwise, the nut may crack depending on the

conditions.

6.35

0 to 0.5

1.0 to 1.5

9.52 0 to 0.5 1.0 to 1.5

90

°

Roughness

Obliquity

A

Die

Pipe

Warp

Outer dia.

R410A

of copper pipe

6.35

1.5 to 2.0

9.52

1.5 to 2.0

Flare nut

Half union

Use a wrench to secure.

Use a torque wrench to tighten.

Externally
threaded side

Internally
threaded side

Rigid (Clutch type)

Imper

Outer dia. R410A Conventional

of copper pipe

tool used tool used

This manual is related to the following products: