Ups is not communicating, Ups is not communicating -4 – StorageTek L700 User Manual
Page 34

Fault Isolation
4-4
First Edition
96047
■
UPS is Not Communicating
The following screen shows what happens if the UPS is not communicating.
The above status might be caused by:
•
Disconnected cables
•
The AP9606 card is not configured properly.
Check the status lights on the card.
Link RX/TX LEDs
Off
The device which connects the Management Card to the
network is turned off or it is not operating correctly.
Flashing
The card is receiving data packets from the network.
Status LED
Indicates the status of the Management Card
Off
The Management Card has no power.
Solid Green
The Management Card has valid network settings.
Flashing Green
The Management Card does not have valid TCP/IP
settings.
Solid Red
A hardware failure has been detected in the
Management Card.
Contact StorageTek’s Customer Support Services.
Flashing Red
The Management Card is making BOOTP requests. If
you do not use a BOOTP server, you need to configure
the Management Card’s TCP/IP settings.