4.3. Indoor unit (Fig. 4-3)

Heat insulation for refrigerant pipes:
1 Wrap the enclosed large-sized pipe cover around the gas pipe, making sure that

the end of the pipe cover touches the side of the unit.

2 Wrap the enclosed small-sized pipe cover around the liquid pipe, making sure

that the end of the pipe cover touches the side of the unit.

3 Secure both ends of each pipe cover with the enclosed bands. (Attach the

bands 20 mm, 25/32 inch from the ends of the pipe cover.)

• After connecting the refrigerant piping to the indoor unit, be sure to test the pipe

connections for gas leakage with nitrogen gas. (Check that there is no refrigerant
leakage from the refrigerant piping to the indoor unit.)

4.4. For twin/triple combination

Refer to the outdoor unit installation manual.

4. Installing the refrigerant piping

5. Drainage piping work

5.1. Drainage piping work (Fig. 5-1)

• Use VP25 (O.D. ø32 mm, 1-1/4 inch PVC TUBE) for drain piping and provide

1/100 or more downward slope.

• Be sure to connect the piping joints using a polyvinyl type adhesive.
• Observe the fi gure for piping work.
• Use the included drain hose to change the extraction direction.

Correct piping

Support metal

Wrong piping

Air bleeder

Insulation (9 mm, 23/64 inch or more)

Raised

Downward slope (1/100 or more)

Odor trap

Grouped piping

O.D. ø32 mm, 1-1/4 inch PVC TUBE

Downward slope (1/100 or more)

Make it as large as possible

O.D. ø38 mm, 1-1/2 inch PVC TUBE for

grouped piping.(9 mm, 23/64 inch or more
insulation)

Indoor unit

Make the piping size large for grouped

piping.

Up to 850 mm, 33-7/16 inch

1.Connect the drain socket (supplied with the unit) to the drain port. (Fig. 5-2)

(Fix the tube using PVC adhesive then secure it with a band.)

2.Install a locally purchased drain pipe (PVC pipe, O.D. ø32mm, 1-1/4 inch).

(Fix the pipe using PVC adhesive then secure it with a band.)

3.Insulate the tube and pipe. (PVC pipe, O.D. ø32mm, 1-1/4 inch and socket)
4.Check that drain fl ows smoothly.
5.Insulate the drain port with insulating material, then secure the material with a

band. (Both insulating material and band are supplied with the unit.)

Unit

Drain pipe (O.D. ø32mm, 1-1/4inch PVC

TUBE)

Insulating material

Insulating material (purchased locally)

Band

Transparent PVC pipe

Drain port (transparent)

O.D. ø32 mm, 1-1/4 inch PVC TUBE (Slope

1/100 or more)

Insertion margin

Drain socket

Matching

Fig. 4-3

Refrigerant pipe and
insulating material

Pipe cover (large)

Pipe cover (small)

Refrigerant pipe (gas)

Refrigerant pipe (liquid)

Band

Cross-sectional view of connection

Pipe

Insulating material

Squeeze

,

Max. 65 ft

5 to 7 ft

Max. 6 inch

Fig. 5-1

Fig. 5-2

(inch)

7/16

1

1

1