Installation location, Installing the indoor unit, Check the indoor unit accessories (fig. 3-1) – Mitsumi electronic MR. SLIM PLA-ABA User Manual

Page 3

background image

3

2. Installation location

Refer to the outdoor unit installation manual.

3. Installing the indoor unit

Fig. 3-1

Fig. 3-2

Fig. 3-3

5-2

9

/32

6-5/16

6-5/16

6-5/16

6-5/16

3-

17

/3

2

33-27/32 to 35-13/16

(5/16)

(5/16)

25/32 to 1-25/32

25/32 to 1-25/32

(inch)

25/32 to

1-25/32

25/32 to

1-25/32

31-7/8

37-3/8

33-1/16

7-3/8

33-1/16

5-5/16

11/16

+3/16

0

11/16

+3/16

0

*

1-15/16

to 2-3/4

*

4-1/8

1-3/8

C

D

Min.

9

8-7/16

Min. 19-11/16

(mm, inch)

Models

A

A12, A18, A24, A30

80, 3-5/32

A36, A42

85, 3-11/32

B

74, 2-29/32
77, 3-1/32

15/16

3-17/32

A

B

*

6-11/16

*

5-1/2

*

7-15/32

2-3/8 11-3/16

14-27/32

23-13/16

-3/16

+1-3/8

33-27/32 to 35-13/16

37-3/8

24-13/32

3.1. Check the indoor unit accessories (Fig. 3-1)

The indoor unit should be supplied with the following accessories.

Accessory name

Q'ty

Installation template

1

Washers (with insulation)
Washers (without insulation)

4
4

Pipe cover (for refrigerant piping joint)
Small diameter
Large diameter

1
1

Band

8

Screw with washer (M5 × 25) for mounting grille

4

Drain socket

1

Insulation

1

3.2. Ceiling openings and suspension bolt installation

locations (Fig. 3-2)

Caution:

Install the indoor unit at least 2.4m (94-1/2inch) above fl oor or grade level.
For appliances not accessible to the general public.

• Using the installation template (top of the package) and the gauge (supplied as

an accessory with the grille), make an opening in the ceiling so that the main unit
can be installed as shown in the diagram. (The method for using the template and
the gauge is shown.)

* Before using, check the dimensions of template and gauge, because they

change due to fl uctuations of temperature and humidity.

* The dimensions of ceiling opening can be regulated within the range shown

in Fig.3-2; so center the main unit against the opening of ceiling, ensuring
that the respective opposite sides on all sides of the clearance between them
becomes identical.

• Use M10 (3/8") suspension bolts.

* Suspension bolts are to be procured at the fi eld.

• Install securely, ensuring that there is no clearance between the ceiling panel &

grille, and between the main unit & grille.

Outer side of main unit

Grille

Bolt pitch

Ceiling

Ceiling opening

Multi function casement (option)

Outer side of Grille

Entire periphery

* Note that the space between ceiling panel of the unit and ceiling slab, etc. must be 10 to 15 mm,

25/64 to 19/32 inch.

*

When the optional multi-functional casement is installed, add 135 mm, 5-5/16

inch to the dimensions marked on the fi gure.

(mm, inch)

Models

C

D

A12, A18, A24, A30

241, 9-1/2"

258, 10-3/16"

A36, A42

281, 11-1/16"

298, 11-3/4"

3.3. Refrigerant and drainage piping locations of
indoor unit

The fi gure marked with * in the drawing represent the dimensions of the main unit
excluding those of the optional multi function casement. (Fig. 3-3)

Drain pipe

Ceiling

Grille

Refrigerant pipe (liquid)

Refrigerant pipe (gas)

Water supply inlet

Main unit

*

When the optional multi-functional casement is installed, add 135 mm, 5-5/16inch

to the dimensions marked on the fi gure.